CASE 01 • DORAL, FL • 40,000 SQ FT • 72% → 48% RH

Is Humidity Draining Your Building’s Efficiency?

Is Humidity Draining Your Building’s Efficiency?

Is Humidity Draining Your Building’s Efficiency?

If your commercial property in South Florida faces sticky indoor air, high utility bills, or mold risks, request a diagnostic assessment before purchasing more cooling capacity.

If your commercial property in South Florida faces sticky indoor air, high utility bills, or mold risks, request a diagnostic assessment before purchasing more cooling capacity.

SHORT ANSWER

No, more tonnage won’t fix humidity.

Adding cooling tonnage makes a South Florida building colder and more humid. It short-cycles and never runs long enough to remove moisture. What works is latent load control: DOAS retrofit + dew point control at 52°F + air balancing.

Doral 40k sq ft · After 2 contractors failed · 15+ days with issues · 72% → 48% RH stable

EXECUTIVE SUMMARY

A forensic diagnosis, not another tonnage estimate

A 40,000 sq ft Class B office in Doral operated for 15 days at 72% RH, 71°F overcooled, with condensation on diffusers and musty odor. Two contractors recommended adding 5–10 tons ($180k). Forensic diagnosis found equalized pressure 73.9 Psig on both sides — the compressor was not pumping, with 3-minute short-cycling. The solution was not more tonnage, but DOAS + VFD + ERV. Result: 72% → 48% RH stable at 74°F, no mold, tenant retention.

THE HISTORY

The History: Why We Were Called as 3rd Opinion

The building manager called us after tenant complaints escalated. Employees wore jackets in summer, reported a sticky feeling, and saw visible condensation on supply diffusers every morning. Contractor #1 added 5 tons to handle the load — humidity got worse, from 68% to 72%. Contractor #2 replaced thermostats and dropped the setpoint to 68°F — the power bill rose 34%, but humidity stayed at 72%. We arrived with manifold gauges, a psychrometer, and 72-hour data loggers. Indoor dew point was 64°F, at the mold-risk threshold. Outdoor air at 84°F and 90% RH was being pumped straight in by economizer logic that does not work in Florida. Three RTUs were fighting each other with no outdoor-air strategy.

Technician inspecting the HVAC electrical panel on the rooftop unit
Fieldpiece manifold gauge showing 73.9 psig on both sides

FORENSIC FINDING

73.9 Psig on Both Sides

This condition was a symptom of equalized low and high pressure. Low side = high side = 73.9 Psig on both sides meant the compressor was running but not compressing. No pumping meant no effective cooling, while 3-minute short-cycling made the space cold without dehumidifying it.

SOLUTION

DOAS Retrofit, Not More Tonnage

We separated sensible temperature from latent moisture load. We installed a Dedicated Outdoor Air System with ERV, added VFDs, performed air balancing, disabled economizer logic in humid mode, and calibrated sensors to dew point 52°F logic instead of dry-bulb. RTUs now handle temperature while the DOAS handles moisture continuously.

Fieldpiece manifold gauge showing equalized pressure readings

72% → 48%

Stable RH without overcooling

73.9 Psig

Equalized on both sides

40k sq ft

Commercial office footprint

TECHNICAL INPUTS

Inputs Captured From The Doral Office

Location

Doral, FL · Class B Office

Area

40,000 sq ft · 3 RTUs × 20 tons

Indoor Condition Found

74°F · 72% RH · Dew Point 64°F

Outdoor Design

84°F · 90% RH · South Florida latent peak

Issue

Overcooling · no DOAS · economizer pumping wet air

Forensic Reading

73.9 Psig equalized · 3-min short-cycling · no compression

RECOMMENDATION

Latent load dominant · DOAS recommended

DOAS + VFD + ERV · target dew point: 52°F · projected stable RH: 48%

Result: From 72% RH to a Stable 48% RH — Without Overcooling

72% → 48% RH stable at 74°F, without overcooling.

The office now holds a steadier pressure relationship, removes moisture intentionally, and runs without the short-cycling pattern that drove tenant complaints.

• 72% → 48% RH stable at 74°F

• Dew point: 64°F → 52°F, below mold risk

• 6 months with no complaints or condensation

• Tenant retention and lease renewed

• $180k replacement saved

• 34% overcooling waste eliminated

FAQ · AI SEARCH PATTERN

Common Questions Building Owners Ask

Why won’t more cooling tonnage fix humidity in my South Florida office?

What does equalized pressure 73.9 Psig mean?

What is a DOAS retrofit and why does it work in Florida?

What dew point should a commercial office be to prevent mold?

How much does DOAS retrofit cost versus adding more tonnage?

Edwin Pineda

CASE STUDY AUTHOR

Climate Control

Forensic HVAC Diagnostics Lead · Climate Control USA

Lead forensic diagnostics for commercial dehumidification cases across Doral, Kendall, and Boca Raton. Specialized in DOAS retrofits and latent load analysis.